This TM3 safety expansion module monitors emergency shutdown pushbuttons and limit switches to conform to PLd / Category 3. It meets the requirements of PL d/Category 3 conforming to EN/ISO 13849-1 and SILCL 2 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has spring terminals for fast and reliable wiring of safety circuits.
Manuals and Documentation
- Catalog Number
- TM3SAC5RG
- Manufacturer
- Schneider Electric
- Brand
- Schneider Electric
- Country of Origin
- France
- Made in USA
- No
- Application
- For emergency stop and switch monitoring
- Display
- for user 6 LEDs (green/red)
- Mounting
- Wall
- Output Signal
- 10 V relay output;Relay instantaneous opening, 3 NO, potential free
- Power Supply
- 100 mA 24 V DC external supply;24 V - 15...20 % DC
- Special Features
- Emergency stop monitoring 1-channel wiring;emergency stop monitoring 2-channel wiring;monitoring of a movable guard with 2 switches and automatic start
- Standard
- Can reach PL d/category 3 ISO 13849-1 2008;can reach PL d/category 3 ISO 13849-2 2012;can reach SILCL 2 IEC 62061 2005;can reach SIL 2 IEC 61508 2010;UL 61010-2-201;CSA 61010-2-201 (pending);TÜV;EAC;CSA Haz Loc Class 1 Division 2 (pending);ANSI Haz Loc Class 1 Division 2 (pending);RCM;ISO 13849-1:2008;ISO 13849-2:2012;IEC 62061:2005;IEC 61508:2010;IEC 60947-5-1:2010;IEC 61131-2:2007;IEC 60204-1:2005;IEC 60204-1:2009/A1;IEC 61010-1:2010;EN 50581:2012;Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2;electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2;susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3;susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3;susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3;magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8;electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4;electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4;1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5;conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6;;CSA;EAC;CE;RCM;UL;TÜV;EFUP 10
- GTIN
- 03606485392981
- Item Type
- Safety module