safety module, Modicon TM3, 1 function, Cat 3 PL d, SIL CL2, screw, 24V DC
MFR: Schneider Electric
MFR #: TM3SAC5R
Item #: 607859
safety module, Modicon TM3, 1 function, Cat 3 PL d, SIL CL2, screw, 24V DC
MFR #: TM3SAC5R
Item #: 607859
Availability
Location | Available Qty |
---|---|
Available | Available to Order |
$465.99
each
This TM3 safety expansion module monitors emergency shutdown pushbuttons and limit switches to conform to PLd / Category 3. It meets the requirements of PL d/Category 3 conforming to EN/ISO 13849-1 and SILCL 2 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability.
Manuals and Documentation
- Catalog Number
- TM3SAC5R
- Manufacturer
- Schneider Electric
- Brand
- Schneider Electric
- Country of Origin
- United States
- Made in USA
- Yes
- Application
- For emergency stop and switch monitoring
- Display
- for user 6 LEDs (green/red)
- Mounting
- Wall
- Output Signal
- 10 V relay output;Relay instantaneous opening, 3 NO, potential free
- Power Supply
- 100 mA 24 V DC external supply at state on);24 V - 15...20 % DC
- Special Features
- Emergency stop monitoring 1-channel wiring;emergency stop monitoring 2-channel wiring;monitoring of a movable guard with 2 switches and automatic start
- Standard
- Can reach PL d/category 3 ISO 13849-1 2008;can reach PL d/category 3 ISO 13849-2 2012;can reach SILCL 2 IEC 62061 2005;can reach SIL 2 IEC 61508 2010;TÜV;CSA 61010-2-201 (pending);CSA Haz Loc Class 1 Division 2 (pending);RCM;ANSI Haz Loc Class 1 Division 2 (pending);EAC;UL 61010-2-201;ISO 13849-1:2008;ISO 13849-2:2012;IEC 62061:2005;IEC 61508:2010;IEC 60947-5-1:2010;IEC 61131-2:2007;IEC 60204-1:2005;IEC 60204-1:2009/A1;IEC 61010-1:2010;EN 50581:2012;Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2;electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2;susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3;susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3;susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3;magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8;electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4;electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4;1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5;conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6;;EFUP 10;RCM;CSA;UL;TÜV;CE;EAC
- GTIN
- 03606485392974
- Item Type