power meter PowerLogic PM5110, modbus, up to 15th Harmonic, 1DO 33 alarms
power meter PowerLogic PM5110, modbus, up to 15th Harmonic, 1DO 33 alarms
Location | Available Qty |
---|---|
Available | Available to Order |
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has one digital pulse output and 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).
Manuals and Documentation
- Catalog Number
- METSEPM5110
- Manufacturer
- Schneider Electric
- Brand
- Schneider Electric
- Country of Origin
- United States
- Made in USA
- Yes
- Accuracy
- Active energy +/- 0.5 %;reactive energy +/- 2 %;active power +/- 0.5 %;apparent power +/- 0.5 %;frequency +/- 0.05 %;power factor +/- 0.5;current +/- 0.5 %;voltage +/- 0.5 %;apparent energy +/- 0.5 %;reactive power +/- 2 %;Class 0.5S active energy IEC 62053-22
- Application
- Power monitoring
- Frequency Rating
- 50 Hz;60 Hz
- Indicator
- 128 x 128 pixels;Monochrome graphic LCD
- Interface
- Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V;JBUS
- Mounting
- Flush
- Special Features
- 64 samples/cycle
- Standard
- UL 61010-1;EN 50470-3;EN 50470-1;IEC 62053-22:2020;IEC 60529;IEC 62053-24;IEC 61557-12:2015;IEC 62053-23:2020;IEC 62052-11:2020;IEC 62052-31:2015;CE IEC 61010-1;cULus UL 61010-1
- GTIN
- 03606480613982
- Item Type
- Power meter;Current;voltage;frequency;power factor;energy;active and reactive power
- Voltage Rating
- 90...450 V AC 45...65 Hz;100...300 V DC