Product Details
The 3RU11 thermal overload relays up to 100 A are designed for current-dependent protection of applications with normal start up conditions against impermissibly high rises in temperature as a result of overload or phase failure. An overload or phase failure causes the motor current to rise above the set rated motor current. This current rise heats up the bimetal strips within the relay via heating elements which, in turn, operate the auxiliary contacts via a tripping mechanism due to their deflection . These switch the load off via a contactor. The switch off time is dependent on the ratio of tripping current to operational current Ie and is stored in the form of a tripping characteristic with long term stability. The Tripped state is signaled by means of a switching position indicator. Resetting takes place manually or automatically after a recovery time has elapsed.
Manuals and Documentation
Features
- 3 A at 24/110/120/125 VAC, 2 A at 230 VAC, 1 A at 400 VAC operating current of auxiliary contacts at AC-15, 1 A at 24 VDC, 0.22 A at 110/125 VDC, 0.11 A at 220 VDC operating current of auxiliary contacts at DC-13
- Direct mounting with vertical mounting surface /-135 deg rotatable, with vertical mounting surface /- 45 deg tiltable to the front and back
- Integrated, sealable cover
- Class 10
- Switching position indication
- Optimized to the 3RT contactors such that in addition to individual mounting they can mounted directly mounted onto the contactors to save space
- Phase failure sensitivity
- Size S2
- Manual, automatic and remote reset
- Reset button
- TEST function
Specifications
Identifiers
| Manufacturer Part Number |
3RU1136-4DB0
|
|---|---|
| GTIN |
00754554412481
|
| UPC |
754554412481
|
|---|---|
| EAN |
4011209300651
|
General Information
| Manufacturer |
Siemens
|
|---|---|
| Brand |
Siemens
|
| Country Of Origin |
DE
|
| Standards Approvals |
RoHS Compliant | REACH Article 33 | CSA Certified | UL Listed | EAC Approved | ATEX Certified | IECEx Certified | ABS Approved | Bureau Veritas CertifiedLRS Listed | RINA Certified | RMRS Approved | DNV-GL Approved
|
|---|---|
| Application |
For standard and overload protection of explosionproof motors
|
Dimensions
| Dimensions |
105 mm H x 55 mm W x 118 mm D
|
|---|
Technical Information
| Amperage Rating |
18 to 25 A
|
|---|---|
| Coil Voltage |
690 V AC
|
| Contact Form |
1NO-1NC 1 Form A/1 Form B
|
| Contact Rating |
25 A at 690 V AC
|
| Enclosure Type |
IP20
|
| Frequency Rating |
50/60 Hz
|
|---|---|
| Mounting Type |
Contactor
|
| Number Of Poles |
3
|
| Temperature Rating |
-20 to 70 deg C
|
| Terminal Type |
Threaded
|