TeSys island direct starter, 3 poles, 65A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 65A and motors up to 30kW@400V / 40hp@480V. It provides motor protection functions including thermal overload (setting 3.35-65A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Manuals and Documentation
- Catalog Number
- TPRST065
- Manufacturer
- Schneider Electric
- Brand
- Schneider Electric
- Warranty Description
- Contractual Warranty:18 months
- Country of Origin
- France
- Made in USA
- No
- GTIN
- 03606489832773