RC816F200SL Homeline Meter Main, CSED, 200 Amp, Ringless, Lever, OH, UG, Outdoor Surface, max 8 Spaces, 16 Circuits
RC816F200SL Homeline Meter Main, CSED, 200 Amp, Ringless, Lever, OH, UG, Outdoor Surface, max 8 Spaces, 16 Circuits
Location | Available Qty |
---|---|
Available | Available to Order |
Homeline All In One combination service entrance devices are available with ring or ringless type meter socket designs. Devices have factory installed service disconnect(s) in most cases. Supplied with 100% branch neutrals, all unused terminals may be used for equipment grounding wires. These Homeline combination service entrance devices meet the Federal Specification W-P-115c as Type 1, Class 2 specifications. This service entrance meter main is supplied with feed thru lugs and has provisions for branch circuit breakers This Homeline combination service entrance meter main unit has a ringless meter socket with lever bypass. This unit can be feed from an overhead or underground service. The service disconnect is a QOM2200-VH which has a maximum rating of 200 A. Device has a 22 kA short circuit current rating. Load center has 8 spaces which will accept up to 8 tandem Homeline circuit breakers. This unit has a NEMA 3R surface mounting enclosure that is 48.62 inches tall, 18.35 inches wide and 5.32 inches deep. The line side lugs will accept 6 AWG to 350 kcmil copper or aluminum wire. The service ground lug will accept 8 AWG to 2/0 AWG copper or aluminum wire. This Homeline combination service entrance meter main unit is UL Listed. Device meets EUSERC standards.