power meter PowerLogic PM5110, modbus, up to 15th Harmonic, 1DO 33 alarms

MFR: Schneider Electric
MFR #: METSEPM5110
Item #: 230991

power meter PowerLogic PM5110, modbus, up to 15th Harmonic, 1DO 33 alarms

MFR #: METSEPM5110
Item #: 230991
Availability
Location Available Qty
Available Available to Order
$1295.48 each

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has one digital pulse output and 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).

Catalog Number
METSEPM5110
Manufacturer
Schneider Electric
Brand
Schneider Electric
Country of Origin
United States
Made in USA
Yes
Accuracy
Active energy +/- 0.5 %;reactive energy +/- 2 %;active power +/- 0.5 %;apparent power +/- 0.5 %;frequency +/- 0.05 %;power factor +/- 0.5;current +/- 0.5 %;voltage +/- 0.5 %;apparent energy +/- 0.5 %;reactive power +/- 2 %;Class 0.5S active energy IEC 62053-22
Application
Power monitoring
Frequency Rating
50 Hz;60 Hz
Indicator
128 x 128 pixels;Monochrome graphic LCD
Interface
Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V;JBUS
Mounting
Flush
Special Features
64 samples/cycle
Standard
UL 61010-1;EN 50470-3;EN 50470-1;IEC 62053-22:2020;IEC 60529;IEC 62053-24;IEC 61557-12:2015;IEC 62053-23:2020;IEC 62052-11:2020;IEC 62052-31:2015;CE IEC 61010-1;cULus UL 61010-1
GTIN
03606480613982
Item Type
Power meter;Current;voltage;frequency;power factor;energy;active and reactive power
Voltage Rating
90...450 V AC 45...65 Hz;100...300 V DC